range of product | C120 |
---|---|
range | Acti 9 |
product name | C120 |
product or component type | Miniature circuit-breaker |
device short name | C120N |
device application | Distribution |
poles description | 2P |
number of protected poles | 2 |
neutral position | Left |
[In] rated current | 63 A at 30 °C |
network type | AC |
trip unit technology | Thermal-magnetic |
curve code | C |
breaking capacity |
10000 A Icn at 230...400 V AC 50/60 Hz conforming to EN/IEC 60898-1 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at <= 250 V DC conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
suitability for isolation | Yes conforming to IEC 60947-2 |
network frequency | 50/60 Hz |
---|---|
[Ue] rated operational voltage |
380...415 V AC 50/60 Hz 220...240 V AC 50/60 Hz 440 V AC 50/60 Hz <= 250 V DC 230...400 V AC 50/60 Hz |
magnetic tripping limit | 5...10 x In |
[Ics] rated service breaking capacity |
7500 A 75 % conforming to EN/IEC 60898-1 - 230...400 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC |
limitation class | 3 conforming to EN/IEC 60947-2 |
[Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-2 |
contact position indicator | Yes |
control type | Toggle |
local signalling | ON/OFF indication |
mounting mode | Clip-on |
mounting support | 35 mm symmetrical DIN rail |
comb busbar and distribution block compatibility | YES |
9 mm pitches | 6 |
height | 81 mm |
width | 54 mm |
depth | 73 mm |
product weight | 0.41 kg |
colour | White |
mechanical durability | 20000 cycles |
electrical durability | 10000 cycles conforming to IEC 60947-2 |
connections - terminals |
Tunnel type terminals1…50 mm² rigid Tunnel type terminals1.5…35 mm² flexible |
wire stripping length | 15 mm |
tightening torque | 3.5 N.m |
earth-leakage protection | Separate block |